Arc occurrence rates are measured for Ag and Pd contacts operated in a DC resistive load circuit. Based on the obtained results, it is confirmed that arc certainly occurs at current levels lower than the conventional minimum arc current value for each of the tested contact materials. Arc occurrence rate in general comes close to 100% at the conventional minimum arc current level. Accordingly, careful attention should be paid to use of the term "minimum arc current" in order to avoid misinterpretation thereof.
The copyright of the original papers published on this site belongs to IEICE. Unauthorized use of the original or translated papers is prohibited. See IEICE Provisions on Copyright for details.
Copy
Makoto HASEGAWA, Yusuke KAMADA, "An Experimental Study on Re-interpretation of Minimum Arc Current of Electrical Contact Materials" in IEICE TRANSACTIONS on Electronics,
vol. E88-C, no. 8, pp. 1616-1619, August 2005, doi: 10.1093/ietele/e88-c.8.1616.
Abstract: Arc occurrence rates are measured for Ag and Pd contacts operated in a DC resistive load circuit. Based on the obtained results, it is confirmed that arc certainly occurs at current levels lower than the conventional minimum arc current value for each of the tested contact materials. Arc occurrence rate in general comes close to 100% at the conventional minimum arc current level. Accordingly, careful attention should be paid to use of the term "minimum arc current" in order to avoid misinterpretation thereof.
URL: https://global.ieice.org/en_transactions/electronics/10.1093/ietele/e88-c.8.1616/_p
Copy
@ARTICLE{e88-c_8_1616,
author={Makoto HASEGAWA, Yusuke KAMADA, },
journal={IEICE TRANSACTIONS on Electronics},
title={An Experimental Study on Re-interpretation of Minimum Arc Current of Electrical Contact Materials},
year={2005},
volume={E88-C},
number={8},
pages={1616-1619},
abstract={Arc occurrence rates are measured for Ag and Pd contacts operated in a DC resistive load circuit. Based on the obtained results, it is confirmed that arc certainly occurs at current levels lower than the conventional minimum arc current value for each of the tested contact materials. Arc occurrence rate in general comes close to 100% at the conventional minimum arc current level. Accordingly, careful attention should be paid to use of the term "minimum arc current" in order to avoid misinterpretation thereof.},
keywords={},
doi={10.1093/ietele/e88-c.8.1616},
ISSN={},
month={August},}
Copy
TY - JOUR
TI - An Experimental Study on Re-interpretation of Minimum Arc Current of Electrical Contact Materials
T2 - IEICE TRANSACTIONS on Electronics
SP - 1616
EP - 1619
AU - Makoto HASEGAWA
AU - Yusuke KAMADA
PY - 2005
DO - 10.1093/ietele/e88-c.8.1616
JO - IEICE TRANSACTIONS on Electronics
SN -
VL - E88-C
IS - 8
JA - IEICE TRANSACTIONS on Electronics
Y1 - August 2005
AB - Arc occurrence rates are measured for Ag and Pd contacts operated in a DC resistive load circuit. Based on the obtained results, it is confirmed that arc certainly occurs at current levels lower than the conventional minimum arc current value for each of the tested contact materials. Arc occurrence rate in general comes close to 100% at the conventional minimum arc current level. Accordingly, careful attention should be paid to use of the term "minimum arc current" in order to avoid misinterpretation thereof.
ER -