[Keyword] power distribution systems(2hit)

1-2hit
  • The Aggregation Point Placement Problem for Power Distribution Systems

    Hideharu KOJIMA  Tatsuhiro TSUCHIYA  Yasumasa FUJISAKI  

     
    PAPER-Graphs and Networks

      Vol:
    E101-A No:7
      Page(s):
    1074-1082

    This paper discusses the collection of sensor data for power distribution systems. In current power distribution systems, this is usually performed solely by the Remote Terminal Unit (RTU) which is located at the root of a power distribution network. The recent rise of distributed power sources, such as photovoltaic generators, raises the demand to increase the frequency of data collection because the output of these distributed generators varies quickly depending on the weather. Increasing data collection frequency in turn requires shortening the time required for data collection. The paper proposes the use of aggregation points for this purpose. An aggregation point can collect sensor data concurrently with other aggregation points as well as with the RTU. The data collection time can be shortened by having the RTU receive data from aggregation points, instead of from all sensors. This approach then poses the problem of finding the optimal location of aggregation points. To solve this problem, the paper proposes a Mixed Integer Linear Problem (MILP) formulation of the problem. The MILP problem can then be solved with off-the-shelf mathematical optimization software. The results of experiments show that the proposed approach is applicable to rather large scale power distribution systems.

  • Malfunction Issue of SiC-SIT Based DC Circuit Breaker in 400 V DC Power Distribution Systems for Data Centers

    Seiya ABE  Sihun YANG  Masahito SHOYAMA  Tamotsu NINOMIYA  Akira MATSUMOTO  Akiyoshi FUKUI  

     
    PAPER-Energy in Electronics Communications

      Vol:
    E95-B No:6
      Page(s):
    1990-1996

    400 V DC power distribution systems for data centers require a fast response DC circuit breaker is required. The semiconductor DC circuit breaker is an important key technology in DC power distribution systems. This paper considers the malfunction of Silicon Carbide- Static Induction Transistor (SiC-SIT) based DC circuit breakers in 400 V DC power distribution systems for data centers. The malfunction mechanism is explained, and a solution is proposed. Investigations are achieved by MATLAB/Simulink and experimental verification.